var f2424comments = new Array(
"Please Mouse over a labelled area for details\nOr Mouse over the PLC model name for a list",
"1)  Ethernet Port\n----------------------\n-  Control & Monitoring via Internet\n-  Remote Programming & SCADA\n-  Built-in MODBUS/TCP Server\n-  F-Server for i-TRiLOGI & ExcelLink\n-  Up to 6 simultaneous Server connections\n-  Send Emails to report real-time events\n-  Connects to other F- or M-series PLCs\n-  Connect to other Modbus/TCP servers\n",
"2)  Analog I/Os\n------------------------\n-  Total 12 independent Analog I/Os\n-  8 channels, 12-bit Analog Inputs (0-5V)\n-  4 channels, 10-bit Analog Outputs (0-5V)\n-  5V precision reference\n-  User-Calibration of all analog I/Os\n-  Directly connect to 4 thermistors\n   (no need to add resistor or signal conditioner)",
"3)  RS485 ports x 2 (COMM2, COMM3)\n-----------------------------------------------\n-  Supports Modbus ASCII & RTU\n-  Can be Mobdbus Master or Slave\n-  Can be for programming/monitoring\n-  Low cost 2-wire networkings\n-  Network up to 255 PLCs each\n-  Programmable baud rate 300-230,400 bps\n-  Programmable parity: None, Even or Odd\n\nApplications:\n    i.  VFD, power meter, analog modules\n    ii. Control of remote I/Os e.g. E10+ PLCs ",
"4)  RS232 port (COMM1)\n--------------------------------\n-  For Programming/Monitoring\n-  Supports Modbus ASCII & RTU\n-  Can be Mobdbus Master or Slave\n-  Programmable baud rate (300-230.4Kbps)\n-  Programmable parity (None, Odd or Even)\n\nApplications:\n   i.  Read from barcode/smartcard readers\n   ii. Send data to serial printer or modem",
"5)  LCD port (Built-in)\n-----------------------------\n-  Support industry-standard character LCD\n-  From 1x8 to 4x20 LCD display\n-  Also support Chinese char. LCD\n\n   (LCD display sold seperately)",
"6)  Power Supply\n------------------------\n-  12 to 24VDC\n-  PLC consumes < 3.5W\n-  Only 0.15A @ 24VDC or 0.3A @12VDC",
"7)  12 Multi-Functions Outputs (5 to 16)\n-------------------------------------------------------\n-  Drive 3 stepper motors DIRECTLY\n-  Or control 3 external stepper motor drivers\n-  4 PWM outputs with adjustable frequency\n-  12 \"lamp dimmer\" outputs\n   (AC phase control)\n-  Drive 4 Infrared Remote Control LEDs\n-  Or use as regular digital outputs\n-  Sink 4A @24VDC per output",
"8)  12 Digital Outputs (1-4, 17-24)\n---------------------------------------------\n-  Sink 1A @24VDC per output\n-  Red LEDs to indicate ON/OFF status",
"9)  Multi-Functions Inputs (1-12)\n------------------------------------------------\n-  3 quadrature High Speed Counters (HSC)\n-  6 Pulse Measurement (PM)\n     (Measure frequency, period, pulsewidth)\n-  HSC coexist with PM (Postiion+Speed)\n-  HSC & PM up to 10KHz\n-  10 channel interrupt inputs\n-  All inputs NPN type (source 3mA per input)",
"10)  Digital Inputs (13-24)\n---------------------------------------------\n-  NPN inputs (source 3mA per input)\n-  Green LEDs to indicate ON/OFF status",
"11)  Battery Back Real Time Clock\n-------------------------------------------\n-  Year, month, day, day of week\n-  Hour, minute, second\n-  Leap year correction\n-  User calibration for greater accuracy\n-  May be adjusted by Internet Time Server\n-  Single CR1632 battery last for > 5 years\n\nApplications:\na. Schedule alarm events to occur.\nb. Time-stamp a data logging event",
"12)  Infra Red Remote Sensor\n-------------------------------------------\n-  Decode Sony Remote Control signal\n-  Learn and store up to 128 IR codes\n    (any brand as long as is about 38KHz)\n-  Playback learned IR codes via output #5-8\n\nApplications:\na. Start/stop equipment\nb. Use as data entry terminal\nc. Enter PIN to unlock equipment\nd. Home Automation/AV Control",
"13)  XBEE Socket Solder Pads\n-------------------------------------------\n-  Solder pads for 2 10-pin SIP sockets\n-  Accept XBEE module made by Digi Int'l\n-  Provide wireless connection via ZigBee radio\n-  Uses COMM2 so must remove RS485 driver\n-  State-of-the-Art Technologies",
"14)  Serial Port Activity LEDs\n-------------------------------------------\n-  A pair of LEDs for each COMM port\n-  GREEN LEDs for Transmit (Tx)\n-  RED LEDs for Receive (Rx)\n-  Blink when there is COMM port activities\n-  Great help for debugging COMM program",
"7)  4 Multi-Functions Outputs (5 to 8)\n-------------------------------------------------------\n-  Drive 1 stepper motor DIRECTLY\n-  Or control 2 external stepper motor drivers\n-  4 PWM outputs with adjustable frequency\n-  4 \"lamp dimmer\" outputs\n   (AC phase control)\n-  Drive 4 Infrared Remote Control LEDs\n-  Or use as regular digital outputs\n-  Sink 4A @24VDC per output",
"8)  12 Relay Outputs (1-4, 9-16)\n---------------------------------------------\n-  Contact ratings: 5A @24VAC/DC per output\n   or 5A @ 120VAC\n   or 2A @ 250VAC\n-  Red LEDs to indicate On/OFF status",
"6)  Power Supply\n------------------------\n-  24VDC Only\n-  PLC consumes < 0.35A (all relays ON)\n-  I/Os can use same or isolated power supply\n-  If I/Os use the same power supply\n   then add load current to select P/S",
"9)  Multi-Functions Inputs (1-12)\n------------------------------------------------\n-  Opto-isolated, bi-directional inputs\n-  9-24V AC or DC (NPN or PNP)\n-  6 high speed inputs forms:\n    i. 3 quadrature High Speed Counter (HSC)\n    ii. 6 Pulse Measurement (PM)\n       (Measure frequency, period, pulsewidth)\n-  HSC coexist with PM (Postiion+Speed)\n-  10 channel interrupt inputs ",
"10)  Digital Inputs (7-16)\n---------------------------------------------\n-  Opto-isolated, bi-directional inputs\n-  9-24V AC or DC (NPN or PNP)\n-  Inputs 7-16 filter out 50/60Hz components\n-  Interface directly to 24VAC signal in HVAC\n-  Green LEDs to indicate ON/OFF status",
"2)  Analog I/Os\n------------------------\n-  Total 12 independent Analog I/Os\n-  8 channels, 12-bit Analog Inputs (0-10V)\n-  4 channels, 10-bit Analog Outputs (0-10V)\n-  10V precision reference\n-  User-Calibration of all analog I/Os\n-  Directly connect to 8 thermistors\n   (no need to add resistor or signal conditioner)"
)

function dispComment1(nodeNumber) {
   if (nodeNumber == -1) {
       document.form1.CommentBox1.value="1) Ethernet Port\n2) Analog I/O\n3) RS232\n4) RS485\n5) LCD port\n6) Power Supply\n7) Multi-function Digital Outputs\n8) Digital outputs\n9) Multi-Function Digital Inputs\n10) Digital Outputs\n11) Battery Back Real Time Clock\n12) Infra Red Remote Sensor\n13) XBEE socket solder pad\n14) LEDs for all 3 serial ports";
       return;
   }
   document.form1.CommentBox1.value =f2424comments[nodeNumber];
}